Red Cross Blood Bank

Constant year round air conditioning with 24/7 temperature sensing and control with second unit operating in duty/standby configuration.

Download PDF
Red Cross Blood Bank Midland, WA used Mitsubishi Electric City Multi VRF heat pump units with 24 hours temperature sensing.

The challenge

The Australian Red Cross Blood Service Midland Donor Centre provides a plasma & whole blood collection service. The blood bank critical store room requires constantly maintained temperature between 20 – 24 degrees. Due to the nature of the equipment in this area, it was essential the temperatures did not go outside of the specified range which demanded a more accurate level of temperature sensing and control than would normally be expected of most DX type air conditioning systems. 

A second unit is required to operate in a duty/standby and backup configuration to provide 24/7 temperature control.

The operation and control of these units also needed to be set up in a way that the controls and configuration could not accidentally be changed at a later date unless specified by the client.

The solution

Mitsubishi Electric Alpha2 simple application controller and AHC M-NET adapters interfaced with five separate PT100 temperature sensor positioned around the room to control two Mitsubishi Electric P series air conditioning units.

A custom Alpha program monitors the 5 x PT100 temperature sensors and controls the units based on the average temperature. This allowed for a much a higher level of temperature control and significantly fewer temperature fluctuations which allowed the units control exactly as required within the desired temperature ranges.

The Alpha rotates the units weekly and brings the second unit on if the temperature deviates from the specified range. Prohibits for mode, set point, on and off were set in the Alpha so that no settings could be inadvertently changed via the use of any of the local or central controllers on site.

Unit Information

Heat Recovery

Air Cooled Heat Recovery

  • Capacity range: 22 to 124 kW
  • 2-pipe heat recovery for simultaneous heating and cooling
  • Reduced condenser footprint
  • External static pressure up to 80 Pa
  • Max. height difference up to 90 m
  • Cooling operation up to 52°C ambient
Read more

Centralised Air Conditioning Controllers

Advanced HVAC Controller

  • Control and monitor third party devices and sensors
  • Display sensor reading and device status on AE-200E centralised controller
  • Interlock third party devices with air conditioning units
  • Digital and analogue signals
Read more